 RR2 Polarity Reversal Relay Module
Model RR2 General Description The RR2 Polarity Reversal Relay Module is intended for use with 2-wire and 4-wire detectors with built-in sounder, such as the following System Sensor models: 2100AT, 2112/24AT, 2112/24ATR and 2112/24AITR. Per NFPA requirements, the RR2 is designed to allow all detectors on a loop to sound when one goes into alarm. The RR2 can differentiate between steady and pulsed panel outputs.
RR2
Product Overview Can be used with a single alarm output panel that provides both coded (pulsed) output for fire and continuous output for burglary. Fulfills NFPA 72 requirement for sounder models Designed for use with System Sensor 2100 Series sounder models Colored wires facilitate easy installation Compatible with 2-wire and 4-wire smoke detectors Can be used with 12 VDC and 24 VDC systems Plug-in quick disconnects for easy wiring
Specifications Operating Voltage Range: Maximum Operating Current Relay Contacts: Operating Temperature Range: Operating Humidity Range: Dimensions: Wire connections: 8.5 to 35 VDC 25mA 2A at 35 VDC 32 to 131 F (0 to 55 C) 5% to 95% non-condensing 2 1/2" x 2 1/2" x 1" 18 AWG stranded, tinned, 16" long
Frequently Asked Questions Q. What advantage does the RR2 have over the RR1? A. The RR2 has the ability to differentiate between continuous and pulsed panel outputs and can be used on single output panels. Q. What panel types are compatible with the RR2? A. The RR2 can be used with 2-wire, 4-wire, 12 VDC or 24 VDC single or combination output panels. Q. Does the RR2 operate with Ademco panels? Are separate Ademco modules also required? A. The RR2 operates with Ademco panels and does not require a separate Ademco module. Q. Does the RR2 operate with continuous and coded (pulsed) alarm signals? A. The RR2 offers a field-selectable switch for setting the RR2 for continuous or coded outputs. Q. Are there any special wiring instructions to follow with the RR2? A. Polarity should be observed and the RR2 must be connected to an auxiliary power supply. Q. What kind of panel outputs are required for use with the RR2? A. The RR2 can be used with fire control panels with a bell/alarm output or an alarm relay output. Q. Does the RR2 accommodate more than one 2-wire sounder detector (2100AT) on a loop? A. Yes, more than one model 2100AT can be placed on a zone when the panel switches to a reverse polarity, noncurrent-limited auxiliary power supply*. Refer to wiring diagrams below for specific 2-wire detector wiring.
* Current supply must be adequate per appropriate calculations.
2-Wire System Triggered from IAC/Bell Circuit:
BELL/ ALARM CIRCUIT (positive signal in alarm state)
PURPLE T+
EOL
BROWN OUT+
UL LISTED ALARM CONTROL PANEL
+
INITIATING CIRCUIT
YELLOW IN+ ORANGE IN-
+ + -
A+ A-
Power
+ + -
A+ A-
Power
-
WHITE OUT-
Not Used
Not Used
+
+
AUX POWER
RED PWR+ BLACK PWR-
+
- RA400Z
- RA400Z
-
2-Wire System Triggered from Alarm Relay Contact:
ALARM RELAY (NO Contact)
PURPLE T+
NOTE: If optional Style A (Class A) wiring is used, a second RR2 module must be added to enable concurrent loop polarity reversal.
EOL
BROWN OUT+
UL LISTED ALARM CONTROL PANEL
+
INITIATING CIRCUIT
YELLOW IN+ ORANGE IN-
+ + -
A+ A-
Power
+ + -
A+ A-
Power
-
WHITE OUT-
Not Used
Not Used
+
+
AUX POWER
RED PWR+ BLACK PWR-
+
- RA400Z
- RA400Z
-
System Sensor Sales and Service
System Sensor Headquarters 3825 Ohio Avenue St. Charles, IL 60174 Ph: 800/736-7672 Fx: 630/377-6495 Documents-on-Demand: 800/736-7672 x3 Web: www.systemsensor.com System Sensor in Canada Ph: 905/812-0767 Fx: 905/812-0771 System Sensor in Europe Ph: + 44.1403.276500 Fx: + 44.1403.276501 System Sensor in China Ph: + 86.29.524.6253 Fx: + 86.29.524.6259 System Sensor in Singapore Ph: + 65.273.2230 Fx: + 65.273.2610 System Sensor in the Far East Ph: + 852.21919003 Fx: + 852.27366580 System Sensor in Australia Ph: + 613.54.281.142 Fx: + 613.54.281.172 System Sensor in India Ph: + 91.11.558.2119 Fx: + 91.11.527.6815
(c)2001 System Sensor. The company reserves the right to change product specifications without notice.
A05-0313-000*3/01(5K)*#733


▲Up To Search▲   

 
Price & Availability of RR2

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X